Functions of power system power quality monitoring instrument

Your current location: home page >> News and information >> technical knowledge

Functions of power system power quality monitoring instrument

Release date:February 27, 2021 Author:Fangchang Electric Power Click:

Power quality monitoring仪Mainly monitoring the power quality status of public power grids or power users. Main technical indicators for power quality monitoring:


1. Voltage deviation: According to the national standard GB/T 12325-2008 "Power Quality - Voltage Deviation of Power Supply", the sum of the positive and negative deviations of 35kV and above power supply voltage shall not exceed 10% of the rated voltage; The allowable deviation of three-phase power supply voltage of 10kV and below is ± 7% of the rated voltage; The allowable deviation of 220V single-phase power supply voltage is -10%~+7% of the rated voltage.


2. Harmonics in public power grids: According to the national standard GB/T14549-1993 "Power Quality - Harmonics in Public Power Grids", the total harmonic distortion rate of the voltage (phase voltage) of public power grids at all levels of 6~220kV is: 5% for 0.38kV, 4% for 6~10kV, 3% for 35~66kV, and 2.0% for 110kV; The allowable value of harmonic current injected into the power grid by users should ensure that the harmonic voltage of all levels of the power grid is within the limit range. Therefore, according to the national standard, the voltage harmonic distortion rate generated by harmonic sources at all levels of the power grid is: 2.6% for 0.38kV, 2.2% for 6-10kV, 1.9% for 35-66kV, and 1.5% for 110kV. For power users of the 220kV power grid and its power supply, refer to this standard for 110kV implementation.


3. Three-phase voltage imbalance: According to the national standard GB/T15543-2008 "Electric Energy Quality - Three-phase Voltage Unbalance", the allowable value of normal voltage imbalance at the public connection point of the power system is 2%, and it cannot exceed 4% in a short time; For each user of a public connection point, the allowable value that causes voltage imbalance at that point is generally 1.3%, and should not exceed 2.6% in a short time.


4. Power system frequency deviation: According to the national standard GB/T15945-2008 "Power Quality - Power System Frequency Deviation", the nominal frequency of China's power system is 50Hz, and the allowable value for normal frequency deviation of the power system is ± 0.2Hz. When the system capacity is small, the deviation can be relaxed to ± 0.5Hz. The standard does not specify the limit of system capacity size. In the National Power Supply Regulations, it is stipulated that the allowable deviation of power supply frequency for power supply bureaus is ± 0.2Hz for power grid capacity of 3 million kilowatts and above, and ± 0.5Hz for power grid capacity of less than 3 million kilowatts.


5. Voltage fluctuation and flicker, as stipulated in the national standard GB/T12326-2008 "Power Quality - Voltage Fluctuation and flicker": the standard stipulates that the long-term (2-hour) flicker value Plt at the public connection point of the power system meets: ≤ 110kV, Plt=0.1 At 110kV, Plt=0.8.


Power system power quality monitoring instrument

This article's website:/news/578.html

Keywords:Power system power quality monitoring instrument,Power quality monitoring device,Development of analytical equipment