Power quality monitoring deviceThe FC-SP100 portable wave recorder produced by the manufacturer is an extension of the generator characteristic tester's functionality. It is a portable device with DSP and embedded operating system as the core, adopting a three-layer architecture to achieve data acquisition, processing, transmission, and storage functions. Based on the advanced data processing capabilities of DSP, FC-SP100 achieves full digital analog signal filtering, which can flexibly adopt different sampling frequencies according to user needs, with a maximum of 100K/S. It can be used for recording and analyzing transient electrical signals. Adopting advanced industrial control kernel and embedded operating system, it efficiently and reliably realizes advanced data processing, transmission, storage, and display functions.
FC-SP100 provides an upper computer software package that can be installed on Windows based computers (upper computers), such as laptops, engineer stations, DCS hosts, etc. The upper computer is connected to FC-SP100 through a fieldbus or local area network to achieve functions such as generator characteristic testing, remote control, and data sharing.
Main functions and features
General starting electrical test of generator: FC-SP100 can facilitate the X-Y characteristic test of any two sets of parameters, such as no-load test, short circuit test, and curve fitting. You can record optional analog waveform curves and RMS curves for excitation regulator related tests, such as step tests, deexcitation tests, load rejection tests, etc. It can conduct generator synchronization test, rotor AC impedance test, phase leading test, etc. Using BF-91 for electrical testing can improve testing efficiency, measurement accuracy, and data processing capabilities, achieving automation of electrical testing.
Fault recording: According to the pre-defined fault criteria by the user, BF-91 monitors the measured signal in real-time, and starts waveform recording when a fault occurs. At the same time, the upper computer is notified, and the recorded data is saved in permanent memory without power loss. This function can be used for monitoring the operation of power systems or other critical equipment, for fault diagnosis and troubleshooting.
Real time monitoring: FC-SP100 is connected to 16 switch signals and 18 analog signals. BF-91 calculates the effective value of analog quantities in real time, calculates quantity values (frequency, active power, reactive power, zero sequence, negative sequence, etc.), and can also calculate harmonics in real time (3 channels can be calculated simultaneously, up to 21 times), vector maps (up to 4 groups, each group can contain up to 6 analog quantities). All the above data, including switch status and analog waveform, can be displayed in real-time. The effective value and switching value can be transmitted in real-time to the upper computer.
Paperless trend chart recording: FC-SP100 can record 16 switching quantities and 8 analog quantities (optional, including calculation quantities) at a frequency of 1 point per second, for a total of 3 days, with cyclic recording to describe the long-term trend of the measured signal. The recorded data does not lose power.
FC-SP100 can be used as a portable instrument for monitoring and analyzing faults in various industrial equipment; It can also be used for online monitoring of key equipment in power systems or other industries; Or use its data processing and computing capabilities as a data source to provide real-time data to other systems.
Technical specifications
18 synchronous sampling analog channels (expandable to 24 channels)
A/D resolution: 16 bits; Effective value accuracy: 0.2% (FSR)
FC-SP100 is equipped with 6 (expandable to 8) analog modules, each consisting of 3 analog channels. Module type:
model | Channel 1 | Channel 2 | Channel 3 |
STM-1001 | AC 0~150V | ||
STM-1002 | AC 0~10A(0~70A) | ||
STM-1003 | DC ±1500V(±300/±30V/±10V/±5V) | ||
STM-1004 | DC 4–20mA | ||
STM-1005 | DC ±1000V | DC ±300V | DC ±100mV |
STM-1006 | Speed signal | DC ±1000V | DC ±100mV |
FC-SP100标准配置 2×STM-1001[UNK]2×STM-1002[UNK]1×STM-1005[UNK]1×STM-1006.
The type configuration of the conditioning module can be adjusted according to user requirements; The range of each conditioning module can be adjusted according to user requirements.
U 16 synchronous sampling switch channels
The standard configuration is an external passive node, which adjusts the internal output of the channel to+24V. It can be configured as active nodes in various voltage ranges according to user requirements.
U synchronous sampling frequency: selectable from 10K/s to 100K/s.
When all 18 analog channels and 16 switch channels are open, the sampling frequency is 10K/s. When opening 2 analog channels and 16 switch channels, the sampling frequency can reach 100K/s.
U 8-channel real-time computing capacity
Calculation accuracy: 0.5% (FSR); The following types of calculation quantities for BF-91:
type | Simulated quantities involved in calculations |
frequency | Communication volume 1, Communication volume 2 (optional), Communication volume 3 (optional) |
Synchronous pressure difference | Terminal voltage, system voltage, phase angle difference (calculation amount) |
Phase angle difference | Communication volume 1, Communication volume 2 |
Two meter method three-phase active power | UABYeah |
Two meter method three-phase reactive power | UABYeah |
Single-phase active power | U、I |
Single-phase reactive power | U、I |
Three phase accumulation and active power | UAIA, UB, IB, UC, IC |
Three phase accumulation and reactive power | UAIA, UB, IB, UC, IC |
positive sequence | Communication volume A, B, C |
negative sequence | Communication volume A, B, C |
zero sequence | Communication volume A, B, C |
Difference between two vectors | Communication volume A, communication volume B |
power factor | Active and reactive power |
Work angle | Active, reactive, and terminal voltage |
U Fault start mode
Analog quantity: sudden change, excessive, insufficient
Switching value: displacement
The fault recording capacity is 1GB and can be expanded according to requirements.
U communication
Serial port: 1 RS-232C port, with a maximum communication baud rate of 115200.
Network interface: 1 10/100Mbps 802.3u interface.
U display screen
6.4 "262144 color TTF display screen
Resolution: 640 × four hundred and eighty
Real time harmonic analysis
Real time harmonic analysis can be performed on three analog channels.
Real time waveform display
Display real-time waveforms in a manner similar to an oscilloscope.
Real time vector graph
Up to 4 vector image screens can be displayed, with each screen displaying up to 6 analog vector images in real-time.
U PC software package
The FC-SP100 PC software package runs on the Windows platform and connects the instrument through a serial or network interface. This includes real-time monitoring, parameter setting, channel calibration, data analysis, and electrical testing for generator overall startup.
U chassis size (mm)
342 (width) × 178 (high) × 318 (deep)
U chassis weight
The net weight of the instrument is approximately 7.5kg.
U working power supply
AC220V 50Hz; DC110-220V; The overall power consumption is about 25W